FC 89 - Last Block

The last block function code marks the end of the function block configuration space. The last block function code is a fixed block located in the highest available block number of the module. The last block cannot be deleted. Additional last blocks cannot be added to the configuration.

 

NOTE: This function code is supported only by the BRC-100/200 and the IMMFP11/12 controllers.

 

In Symphony systems, the last block function code has one output. The output indicates the special operations options configuration including the module network type, time-stamping, Hnet cable length, and revision checking. Special operations are documented in the installation section of the individual controller's product instruction.

 

Outputs:

Blk

Type

Description

0-9999

R

Special operations options configuration

Network type

X0X0 = Plant loop

X0X1 = Cnet

X0X3 = Cnet with time-stamping

 

Hnet cable length (BRC-100/200 only)

X00X = 1200m

X02X = 3000m

X03X = 2000m

X04X = 800m

 

Revision check (BRC-100/200 only)

00XX = Revision check disabled

10XX = Revision check enabled

 

 

 

 

 

Specifications:

Spec

Tune

Default

Type

Range

Description

S1

N

0

I

-32,768 to +32,767

Reserved Signed Integer