FC 242 - DSOE Digital Event Interface

The digital event interface block provides the parameters needed to control the IMSET01 distributed sequence of events time module and the IMSED01 distributed sequence of events digital module.

 

NOTE: This function code is supported by the BRC-100, IMMFP11/12 and HAC controllers.

 

This function code is required for both the BRC-100 controller and the INSEM01 distributed sequence of events module to configure a distributed sequence of events system.

 

 

 

Outputs:

Blk

Type

Description

N

B

Output 1 with quality

N+1

B

Output 2 with quality

N+2

B

Output 3 with quality

N+3

B

Output 4 with quality

N+4

B

Output 5 with quality

N+5

B

Output 6 with quality

N+6

B

Output 7 with quality

N+7

B

Output 8 with quality

N+8

B

Output 9 with quality

N+9

B

Output 10 with quality

N+10

B

Output 11 with quality

N+11

B

Output 12 with quality

N+12

B

Output 13 with quality

N+13

B

Output 14 with quality

N+14

B

Output 15 with quality

N+15

B

Output 16 with quality

N+16

B

Module status:

0 = good

1 = bad

 

 

 

Specifications:

Spec

Tune

Default

Type

Range

Description

S1

N

0

I

0 - 63

Address of SET/SED input module

S2

N

2

I

Note 1

Block address of next digital event interface (function

code 242)

S3

Y

10

I

Full

Debounce filter time value (in msecs)

S4

Y

0

I

Full

Input scan mask

0 = channel in-scan

1 = channel out-of-scan

S5

Y

50

I

0 - 8192

Channel 00 TON

S6

Y

50

I

0 - 8192

Channel 00 TOFF

S7

Y

50

I

0 - 8192

Channel 01 TON

S8

Y

50

I

0 - 8192

Channel 01 TOFF

S9

Y

50

I

0 - 8192

Channel 02 TON

S10

Y

50

I

0 - 8192

Channel 02 TOFF

S11

Y

50

I

0 - 8192

Channel 03 TON

S12

Y

50

I

0 - 8192

Channel 03 TOFF

S13

Y

50

I

0 - 8192

Channel 04 TON

S14

Y

50

I

0 - 8192

Channel 04 TOFF

S15

Y

50

I

0 - 8192

Channel 05 TON

S16

Y

50

I

0 - 8192

Channel 05 TOFF

S17

Y

50

I

0 - 8192

Channel 06 TON

S18

Y

50

I

0 - 8192

Channel 06 TOFF

S19

Y

50

I

0 - 8192

Channel 07 TON

S20

Y

50

I

0 - 8192

Channel 07 TOFF

S21

Y

50

I

0 - 8192

Channel 08 TON

S22

Y

50

I

0 - 8192

Channel 08 TOFF

S23

Y

50

I

0 - 8192

Channel 09 TON

S24

Y

50

I

0 - 8192

Channel 09 TOFF

S25

Y

50

I

0 - 8192

Channel 10 TON

S26

Y

50

I

0 - 8192

Channel 10 TOFF

S27

Y

50

I

0 - 8192

Channel 11 TON

S28

Y

50

I

0 - 8192

Channel 11 TOFF

S29

Y

50

I

0 - 8192

Channel 12 TON

S30

Y

50

I

0 - 8192

Channel 12 TOFF

S31

Y

50

I

0 - 8192

Channel 13 TON

S32

Y

50

I

0 - 8192

Channel 13 TOFF

S33

Y

50

I

0 - 8192

Channel 14 TON

S34

Y

50

I

0 - 8192

Channel 14 TOFF

S35

Y

50

I

0 - 8192

Channel 15 TON

S36

Y

50

I

0 - 8192

Channel 15 TOFF

S37

Y

0

I

0 - 8192

Spare

S38

Y

0.000

R

0 - 8192

Spare

 

NOTE:

1. Maximum values are: 9,998 for the BRC-100, IIMMFP11/12 and 31,998 for the HAC

 

 

 

242.1   Explanation

 

242.1.1   Specifications

 

S1

Bus address configured through dipswitches on the SET/SED board.

 

NOTE: For the SET board of a single BRC-100 controller, function codes 241 and 242 are configured for the same I/O module board.

 

S2

Block address for the next digital event interface (function code 242). Function codes 241 and 242 form a linked list that describes the SET/SED configuration for the BRC-100 controller.

 

S3

Time interval (in milliseconds) used on the SET/SED board to tell the valid state transitions and noise spikes apart.

 

S4

16-bit mask that describes the desired configuration for the input channels on the I/O module board.

0 = channel in-scan

1 = channel out-of-scan

 

S5 through S36

Channels 00 TON through 15 TOFF are time values that are subtracted from the registered transition time values to get the correct time-stamp for the transition. The values depend on the physical characteristics of the transducer used.

 

S37 and S38

Spare.