FC 20 - Indicator Station

This function transmits up to three real values to the NDIS01 Digital Indicator Station. The input to this function block must come from an analog exception report (function code 30) or a digital exception report (function code 45) block.

 

NOTE:

A block address must be specified for all three inputs or the digital indicator station will not cycle through the channels using the VAR button.

 

 

Outputs:

Blk

Type

Description

N

I

No usable output

 

 

Specifications:

Spec

Tune

Default

Type

Range

Description

S1

N

0

I

Note 1

Block address of input # 1

S2

N

0

I

Note 1

Block address of input # 2

S3

N

0

I

Note 1

Block address of input # 3

S4

N

0

I

Note 1

Indicator Station Address

NOTE:

1. Maximum values are:           254 for COM modules and CLC01/02/03/04

1023 for SLC01/21

2046 for NMFC01/02, IMMFC05 and CBC01

9998 for IMMFC03/04 and IMMFP01/02/03